Atlanta
Peachtree Corners
Developed by
ASHRAE Technical Committee 9.7, Educational Facilities
Design Guidance for
Education Facilities:
Prioritization for
Advanced Indoor Air Quality
© 2023 ASHRAE
180 Technology Parkway · Peachtree Corners, GA 30092 · www.ashrae.org · All rights reserved.
This document was developed by
ASHRAE Technical Committee (TC) 9.7, Educational Facilities.
ASHRAE TC 9.7 is concerned with the application of heating, ventilating,
air-conditioning, refrigeration, life safety, and energy conservation systems to
educational facilities.
Primary Contributing Authors
Raj Setty, PE, CxA, LEED AP Kyle Hasenkox
Christopher Ruch Keith Hammelman, PE
Corey Metzger, PE Itzhak Maor, PE, PhD
ASHRAE is a registered trademark in the U.S. Patent and Trademark Office, owned by the American Society of
Heating, Refrigerating and Air-Conditioning Engineers, Inc.
ASHRAE has compiled this publication with care, but ASHRAE has not investigated, and ASHRAE expressly
disclaims any duty to investigate, any product, service, process, procedure, design, or the like that may be described
herein. The appearance of any technical data or editorial material in this publication does not constitute endorsement,
warranty, or guaranty by ASHRAE of any product, service, process, procedure, design, or the like. ASHRAE does
not warrant that the information in the publication is free of errors, and ASHRAE does not necessarily agree with any
statement or opinion in this publication. The entire risk of the use of any information in this publication is assumed
by the user.
No part of this publication may be reproduced without permission in writing from ASHRAE, except by a reviewer
who may quote brief passages or reproduce illustrations in a review with appropriate credit, nor may any part of this
publication be reproduced, stored in a retrieval system, or transmitted in any way or by any means—electronic,
photocopying, recording, or other—without permission in writing from ASHRAE. Requests for permission should
be submitted at www.ashrae.org/permissions.
Contents
Intent and Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Prioritization for Advanced IAQ: Checklists . . . . . . . . . . . . . . . 5
Prioritization for Advanced IAQ: Budgetary Guidelines . . . . . . 6
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Ventilation Verification and Testing and Balancing of HVAC
Airside Components (Existing Facilities Only). . . . . . . 8
Risk Tolerance Assessment–Wells-Riley or Equivalent . . 11
Very High Priority Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
HVAC Equipment Filtration Upgrades . . . . . . . . . . . . . . . . 14
HVAC for Wellness/Nurse Suites for Pre-K–12 . . . . . . . . . 16
Classroom and Assembly Space Air Distribution and
Dilution Effectiveness . . . . . . . . . . . . . . . . . . . . . . . . 19
High Priority Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
IAQ Sensors with Data Aggregation Platform . . . . . . . . . . 21
New HVAC Equipment to Achieve ASHRAE-Recommended
Air Change Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Classroom-Level Air Cleaning . . . . . . . . . . . . . . . . . . . . . . 24
Restroom Exhaust and Air Filtration Upgrades . . . . . . . . . 27
Staff Training and Documentation Organizational
Platform . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
UV-C/UVGI in Air Handling Equipment . . . . . . . . . . . . . . . 29
Medium Priority Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Humidification and Dehumidification Systems. . . . . . . . . . 32
Energy Efficiency Offset Control Schemes for
Advanced IAQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Operable Windows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
4 Design Guidance for Education Facilities
Intent and Scope
The intent and scope of this document is to provide guidance to owners, oper-
ators, designers, and professional service providers on how to best implement
indoor air quality (IAQ) improvements, including risk mitigation strategies, in
educational facilities. It will also help facilitate discussion between designers and
stakeholders, identify minimum recommendations, and discuss further consider-
ations to improve IAQ and reduce the transmission risk of infectious pathogens
and other contaminants of concern.
Purpose
This document should be used to prioritize decisions related to heating, venti-
lating, and air-conditioning (HVAC) system design and operation for existing
facilities (commissioning, maintenance, improvement, and retrofit projects) and
new facilities to improve indoor air quality while limiting energy consumption.
IAQ upgrades can improve learning outcomes and mitigate the risk of trans-
mission of airborne pathogens within the educational environment.
This guide is intended to help qualified professionals, including HVAC engi-
neers; commissioning agents; testing, adjusting, and balancing (TAB) providers;
and facility managers assess existing facilities and identify appropriate design
decisions for new facilities. Every school, and its HVAC systems, is unique and
requires its own distinct solutions. This document provides prioritization themes
but does not replace the efforts of a qualified professional in assessing each facil-
ity’s unique characteristics.
This document is broken into several sections including Prerequisite Tasks,
Very High Priority Tasks, High Priority Tasks, and Medium Priority Tasks. Within
each of these sections are steps or HVAC system strategies for consideration, typ-
ically with base minimum and advanced IAQ strategies, targets, or requirements.
The “base minimum” recommendations, beyond code requirements, should be
implemented to meet a minimum level of air quality and risk mitigation. These
strategies were developed through collaboration and review by members of
ASHRAE Technical Committee 9.7, Educational Facilities, and members of the
Epidemic Task Force (ETF) Schools Team. The recommended strategies have
been implemented across many educational facility systems worldwide.
The “advanced IAQ” recommendations are generally believed to represent
best practices that may not be appropriate for all applications but are worth con-
sideration for adoption to improve beyond the base minimum recommendations.
Various combinations of these strategies have been implemented in facilities to
address concerns related to airborne pathogens and indoor air quality in general.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 5
Prioritization for Advanced IAQ:
Checklists
Complete Prerequisite Tasks
Ventilation verification and testing, adjusting, and balancing (TAB) of HVAC
airside components
Risk tolerance assessment—Wells-Riley or equivalent
Base Improved Advanced Very High Priority Tasks
HVAC equipment filtration upgrade
HVAC for wellness/nurse suites for pre-K–12
Classroom and assembly space air distribution
effectiveness
Base Advanced High Priority Tasks
IAQ sensors with data aggregation platform
New HVAC equipment to achieve ASHRAE-recommended air
change rates (ACH)
Classroom-level air cleaning
Restroom exhaust and air filtration upgrades
Staff training and documentation organizational platform
UV-C/UVGI for air handlers
Base Advanced Medium Priority Tasks
Humidification and dehumidification systems
Energy efficiency offset control schemes for advanced IAQ
Operable windows
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
6 Design Guidance for Education Facilities
Prioritization for Advanced IAQ:
Budgetary Guidelines
Note: The budgetary numbers are to be used for capital planning and does not
substitute for an actual design and construction bid process. The general ranges
can be adjusted based on local and climatic conditions. Users should budget 5%
yearly escalation in the cost ranges after 2023. Budgets will vary based on the age
and condition of the school and HVAC systems. Budget costs assume minimal
architectural work. Structural, phasing, temporary equipment, electrical or plumb-
ing upgrades, extensive demolition of existing system, and replacement of spe-
cialty finishes are not included in the ranges.
Low High Units Prerequisite Tasks
$0.35 $0.60 ft
2
Ventilation verification assessment
$5000 $15,000 Building Risk tolerance assessment—Wells-Riley or equivalent
Low High Units Very High Priority Tasks
$0.30 $1.50 cfm HVAC equipment filtration upgrade
$350 $500 ft
2
HVAC for wellness/nurse suites for pre-K–12
$0.20 $0.35 ft
2
Classroom and assembly space air distribution effectiveness
Low High Units High Priority Tasks
$0.50 $1.00 ft
2
IAQ sensors with data aggregation platform
$5.00 $10.00 ft
2
New HVAC equipment to achieve ASHRAE-recommended
ACH
$1000 $2000 Classroom Classroom-level air cleaning
$1500 $3000 Restroom Restroom exhaust and air filtration upgrades
$1500 $2000 Cost/person/
week
Staff training and documentation organizational platform
$0.35 $0.70 cfm UV-C/UVGI for air handlers
Low High Units Medium Priority Tasks
$1.50 $4.00 cfm Humidification and dehumidification systems
$15,000 $35,000 Site Energy efficiency offset control schemes for advanced IAQ
$1500 $3,500 Window Operable windows
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 7
Prerequisites
Establishing an IAQ building-level improvement plan is a process that
involves several components. These prerequisites are about establishing objectives
and existing conditions (where applicable). Without these initial steps, it is not
possible to develop a comprehensive strategy to mitigate risk and maintain a high
level of IAQ. It is important to understand that these strategies reduce, but do not
eliminate, the potential for airborne transmission and must be used as part of a
comprehensive layered risk management approach. It should also be noted that
while the current focus may be on SARS-CoV-2/COVID-19, improving indoor air
quality in education facilities will have similar benefits for other airborne patho-
gens, and studies have shown reduced absenteeism and better performance from
students in facilities with better indoor environments.
The first step is to determine the appropriate level of risk tolerance/mitigation
and associated general system operating characteristics. Once this step has been
completed, the required scope of work for existing facilities or new facilities
should be developed. Factors include, but are not limited to, identifying and prior-
itizing buildings needing improvements, which systems are currently in place, and
whether those systems function as intended. Much of the initial data collection
can be completed by reviewing existing records and documentation where avail-
able. The data may come from record drawings, manuals, control systems, per-
sonnel interviews, or maintenance records. The initial data collection process may
be shared between facility stakeholders including administrative, maintenance and
operations, and HVAC professionals as needed to collect the summary of the sys-
tems to be analyzed.
From this initial facility and equipment list, a scope of work can be generated
to verify the system performance. An HVAC professional should be engaged to
help develop the plan for assessment of the existing equipment and establish a
ventilation verification and testing and balancing of HVAC airside components
plan. A combination of the records and verification reports will create an accurate
picture of the existing systems and their condition.
Next, an initial assessment of HVAC risk can be determined using site-specific
risk analysis tools such as the Wells-Riley Equations, Equivalent Outdoor Air
Rate Calculator, and/or other assessment tools. The resulting analysis should give
an estimate of the risk in specific spaces and may help develop an equitable strat-
egy between facilities and spaces with varying configurations. There are several
mitigation strategies that effect other components of risk, such as common areas,
but the establishment of a summary of the existing conditions and discussion of
risk acceptance are critical in the development of a comprehensive plan, which is
why they are considered prerequisites to the process. While variations of these
prerequisites will exist in different facilities and areas, the inclusion of this pro-
cess and the discussion of it between stakeholders and HVAC professionals is
foundational in the process.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
8 Design Guidance for Education Facilities
Ventilation Verification and Testing and Balancing of
HVAC Airside Components (Existing Facilities Only)
Overview
Perform a physical assessment of existing HVAC infrastructure and provide a
written condition assessment. Verify operation and conditions of existing systems.
This baseline assessment must be performed by a skilled, trained, and certified
technician. Upon completion, the assessment should be submitted to an HVAC
design professional for determination of adjustments, replacements, repairs, and
upgrades. Where possible, this can be compared to record drawings, manuals, and
noted deficiencies in performance.
Involved Parties
A skilled, trained, and certified technician performs the physical assessment in
coordination with facilities personnel and a qualified design professional, as
defined by state or provincial guidelines.
Procedure
Refer to Additional Guidance for sample ventilation verification assessment
test sheets and method of procedures (MOP). Sample procedures should be
altered to meet local requirements, updated recommendations, and site-specific
equipment.
Base Minimum
For All Airside Systems
Document filter Minimum Efficiency Reporting Value (MERV) values
and ensure proper installation with minimum bypass air.
Physically verify and document ventilation rates. Adjust the ventilation
rates to accommodate the building elevation and corresponding air den-
sity per ASHRAE Standard 62.1, Ventilation and Acceptable Indoor Air
Quality (6.2.1.1.3).
Physically verify demand control ventilation (DCV) operates as intended.
A minimum of 10% sampling is acceptable for verification. If carbon
dioxide is used as a surrogate for occupancy, confirm sensors are installed
at space level (not in common return) and confirm calibration of sensors
(minimum of five per facility or 10%).
Document initial and periodic calibration procedure and implement with
calibration period not to exceed five years.
Air distribution: Measure a minimum of 10% of all zones/inlets/outlets
for a cfm sampling. These should be representative of the overall HVAC
system. Zones measured should be representative of zones in system
(closest and furthest from equipment, interior and exterior spaces, etc.).
Document building differential pressures of rooms temporarily occupied
by sick students and staff (i.e., nurses’ isolation rooms). Pressure should
be read between space of concern and adjacent occupied area(s).
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 9
Document existing sequence of operations (SOP/SOO) and operational
controls.
Document ambient outdoor CO
2
conditions and differential to indoor
spaces. Trend the CO
2
levels over the duration of peak occupancy. If CO
2
levels exceed recommended limits (typically outside air level +750 ppm
set point or 1100–2000 ppm) for 90 minutes, further recording should be
implemented. Recommended limits are based on ASHRAE TC 9.7 mem-
ber author’s design experience.
Perform testing of PM
2.5
, PM
10
, and VOC levels in a minimum of 10%
of the spaces hourly during occupied times over a minimum period of one
week.
Verify that equipment is operating as outlined in the SOP/SOO.
Report and remediate any issues and coordinate with the qualified design
professional.
Exhaust
Air distribution: Survey a minimum of 10% of all exhaust inlets, with
measurements taken in areas that will represent operation throughout the
system. Ensure that systems are all operating in occupied mode.
Figure 1 Testing and balancing of HVAC airside components.
Source: www.nemionline.org/testing-adjusting-and-balancing-hvac-
systems-an-overview-of-certification-agencies/
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
10 Design Guidance for Education Facilities
Limited or No Existing Mechanical Ventilation
In cases where there is limited or no existing mechanical ventilation, the
assessment should focus on available strategies to provide ventilation including,
but not limited to, operable windows and building chases. Provide the qualified
design professional with documentation for future ventilation improvements for
concurrence.
Advanced IAQ
For All Airside Systems
Determine air handler capability to accommodate MERV 13 filter.
Verify physical ability to increase ventilation above scheduled value.
Verify physical ability to override and/or disable the DCV.
Measure 100% of all air distribution inlets/outlets.
Document building pressure relationships of all rooms as recommended
by your HVAC professional.
Test a minimum of 10% of sensors for accuracy and document the drift of
the sensors in comparison to handheld sensor readings. Calibrate sensors.
Verify operational controls respond correctly.
Schedule a periodic physical ventilation verification assessment of pri-
mary HVAC systems every five years.
Establish a verification and calibration program to confirm operation of
sensors.
Exhaust
Survey 100% of all air distribution exhaust inlets for a sampling.
Additional Guidance
ASHRAE TC 7.7, Testing and Balancing.
Meyers, F., and T. Pistochini. 2020. Testing, adjusting and balancing HVAC sys-
tems: An overview of TAB certification agencies. WCEC technical report.
Davis, CA: University of California Davis Western Cooling Efficiency Center.
https://wcec.ucdavis.edu/wp-content/uploads/TAB-Technical-Report-
051220.pdf.
Associated Air Balance Council (AABC).
National Environmental Balancing Bureau (NEBB).
Testing, Adjusting and Balancing Bureau (TABB).
IEQ Guidelines. 2022. Copy of all IAQ guidelines reports. https://ieqguide-
lines.org/table.html.
NEMI. 2022. Sample ventilation verification assessment test sheets. https://
www.nemionline.org/vvr-for-contractors/.
NEMI. 2022. Ventilation verification specification. https://www.nemionline.org/
ventilation-verification-specification/.
Ruch, C., and T. Pistochini. 2021. White paper: Proposed ventilation and energy
efficiency verification/repair program for school reopening. NEMI/University
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 11
of California Davis Energy and Efficiency Institute. https://ucda-
vis.app.box.com/v/ProposedVentilationProgram.
UC Davis Energy. 2020. Importance of ventilation in schools. YouTube video,
produced by University of California Davis Western Cooling Efficiency Cen-
ter. https://www.youtube.com/watch?v=F9hB9BgonHs.
Risk Tolerance Assessment–
Wells-Riley or Equivalent
Overview
When prioritizing IAQ projects and budgeting, start with a baseline of the cur-
rent probability of infection. Establish a target goal for the probability of transmis-
sion of infectious airborne assessments, based on HVAC and operational changes.
A risk assessment should be performed as part of the basis of design for any IAQ
upgrade project.
Designers and engineers need to evaluate their design approaches for effec-
tiveness in reducing the risk of transmission. The calculation tool may be used to
compare HVAC options against each other to balance effectiveness and budgetary
constraints.
It is recommended that the stakeholders determine the acceptable level of risk
as defined by their governing bodies.
Involved Parties
Design engineers, facility managers, architects, building operations staff, and
local health officials.
Base Minimum
While there are no 100% solutions to ensure no one will be infected by a virus
in a common space like a classroom, there are operational and HVAC system
changes that reduce the airborne concentration of viruses. The underlying direc-
tive for HVAC engineers is “do no harm.” The application of better filtration,
reduction in exposure time, reduction in occupancy, more fresh air to the building
spaces, and disinfection of the airstream via UV-C all have positive impacts to the
indoor air quality. While there are cost implications to the various applications,
the risk of negatively impacting the IAQ is almost negligible.
Below are some examples of available risk analysis tools. The site-specific
strategy employed should be developed in collaboration with stakeholders and
your HVAC professional. Note that inclusion of these calculators is to provide
examples of risk assessment tools and is not an endorsement of the tool itself.
2020 COVID-19 Aerosol Transmission Estimator
Harvard-CU Boulder Portable Air Cleaner Calculator for Schools, v1.3
SETTY-5.2, Small Space Airborne Transmission Infection Rate Estimator
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
12 Design Guidance for Education Facilities
Wells-Riley Equation
where
Advanced IAQ
Advanced IAQ risk assessments should address both the probability of infec-
tion as well as air cleaning strategies. Advanced IAQ assessments should also
address specific airborne contaminants beyond the base IAQ risk assessments.
The site-specific strategy employed should be developed in collaboration with
stakeholders and your HVAC design professional. Advanced IAQ risk assess-
ments should employ a layered mitigation strategy to reduce the probability of
contaminant transmission.
The Wells-Riley model (Fisk et al. 2005; Nazaroff et al. 1998) is used for par-
ticle removal and air disinfection (UV-C, UVGI).
Add to the equation:
Additional Guidance
Bahnfleth, W.P. 2020. Reducing infectious disease transmission with UVGI.
Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/file%20library/
professional%20development/learning%20portal/instructor-led%20training/
online%20instructor-led/final-4-21-2020-ashrae-one-hour-uvgi-course_se-
cured.pdf.
EPA. 2022. Simulation tool kit for indoor air quality and inhalation exposure
(IAQX). https://www.epa.gov/air-research/simulation-tool-kit-indoor-air-
quality-and-inhalation-exposure-iaqx.
P
infection
= probability of infection
C = number of infection cases
S = number of susceptible
I = number of infectors
p = pulmonary ventilation rate of a person
q = quanta generation rate (based on the estimated epidemi-
ological outbreak use case)
t = exposure time interval
V = volume of the room
Q = room ventilation rate with clean air
infection
1

--------


1+
2
------------------------------
=
UV = rate coefficient of inactivation by ultraviolet irradiation
Qr = flow rate to the filter
r = filtration efficiency
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 13
Fisk, W.J., O. Seppänen, D. Faulkner, and J. Huang. 2005. Economic benefits of
an economizer system: Energy savings and reduced sick leave. ASHRAE
Transactions 111(2): 673–79.
Nazaroff, W.W., M. Nicas, and S.L. Miller 1998. Framework for evaluating mea-
sures to control nosocomial tuberculosis transmission. Indoor Air 8: 205–18.
NIST. 2022. ViPER—Virus particle exposure in residences tool. https://
pages.nist.gov/CONTAM-apps/webapps/ViPER/.
Sze To, G.N., and C.Y.H. Chao. 2010. Review and comparison between the Wells-
Riley and dose-response approaches to risk assessment of infectious respira-
tory diseases. Indoor Air 20(1): 2–16. https://www.ncbi.nlm.nih.gov/pmc/arti-
cles/PMC7202094/.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
14 Design Guidance for Education Facilities
Very High Priority Tasks
HVAC Equipment Filtration Upgrades
Overview
By improving the filtration in the air handlers, it is possible to decrease the
chance of aerosolized viral particles being spread through the air distribution system.
While higher filtration is more effective, it may not be practical, because there
are diminishing returns in improvement of particulate removal and increases in
static pressure and cost. Additionally, existing equipment may have several limita-
tions such as fan static capacity. Higher levels of filtration are better; however,
research has determined that diminishing returns in the effectiveness of particle
removal begin at MERV 13 to MERV 14 filter ratings.
An increase from MERV 8 or MERV 11 represents a substantial increase in
the efficacy of filtration of small infectious particles. Filter frame size should be
evaluated by your HVAC professional to handle the filter upgrade. If the filter
frame cannot be increased, proceed with the highest level MERV filter that will
not require the equipment or ductwork to be changed. The introduction of new fil-
Figure 2 MERV filter models.
Source: Kowalski, W.J., and W.P. Bahnfleth. 2002. MERV filter models for
aerobiological applications. Air Media, Summer.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 15
ters may create higher O&M and energy costs plus a higher pressure drop, the
impacts of which should be reviewed by your HVAC professional.
Involved Parties
Design engineers, facility managers, architects, TAB contractor/technician,
and building operations staff.
Base Minimum
Assess existing filtration levels and create an inventory of existing filtra-
tion efficiency (per ASHRAE Standard 52.2) and ventilation volumes.
Assess ventilation system capacity for higher levels of filtration, includ-
ing motor and physical dimensions of air handlers.
Apply the highest MERV filter for the HVAC units (local, central, and
DOAS) given limitations with increased pressure drop. MERV 13 is the
recommended minimum.
Create and follow safe procedures for filter maintenance and operations
per the Occupational Safety and Health Administration (OSHA) and
ASHRAE Standard 180.
Verify airflows after filtration level changes.
Monitor loading pattern on filters after changes and adjust filter change
schedules to meet new loading patterns.
Label all filters with the manufacturer’s name showing the MERV rating
and date of filter change.
Advanced IAQ
Make duct modifications where required to ensure that a minimum level
of MERV 13 is reached in all areas and MERV 14 where possible.
Consider adding differential pressure sensors to monitor the status of filters.
Consider alternate filter locations in return duct or grille, but consider static
pressure drop implications and relationship with outside air dampers.
Consider the addition of a prefilter to extend primary filter life.
Consider UL-listed electrostatic devices.
Consider adding HEPA filters in critical/ higher density areas with lower
outside air volumes.
Consider additional treatment technology to inactivate airborne infectious
aerosols (refer to the ASHRAE Epidemic Task Force’s document for
reopening schools and universities for additional guidance).
Consider having facility staff who perform filter change-out procedures
to be trained for proper installation and maintenance of new filters and air
cleaning systems.
Additional Guidance
ASHRAE. 2017. ASHRAE Standard 52.2-2017, Method of testing general venti-
lation air-cleaning devices for removal of efficiency by particle size. Peachtree
Corners, GA: ASHRAE. https://www.techstreet.com/ashrae/standards/ashrae-
52-2-2017?product_id=1942059.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
16 Design Guidance for Education Facilities
ASHRAE. 2021. ASHRAE position document on filtration and air cleaning.
Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/file%20library/
about/position%20documents/filtration-and-air-cleaning-pd-feb.2.2021.pdf.
EPA. 2022. What is a MERV rating? https://www.epa.gov/indoor-air-quality-iaq/
what-merv-rating.
UC Davis Energy. 2021. The importance of filtration in schools. YouTube video,
produced by University of California Davis Western Cooling Efficiency Cen-
ter. https://www.youtube.com/watch?v=ycgLBUfIM_c.
HVAC for Wellness/Nurse Suites for Pre-K–12
Overview
This section focuses on the educational facility’s wellness/nurse suite where
students with medical issues are placed during the period prior to them being
transferred out of the facility. It is intended to be a transitory space to temporarily
hold potentially infectious persons. Due to the operation of many facilities, this
space is often located at or near the central office, which also acts in a security
role by controlling access to the facility. The combination of keeping a potentially
infectious person near a specifically designed point where all traffic is being
routed presents an increased level of risk, and additional consideration of strate-
gies to mitigate this risk may be warranted.
The facility size should be considered along with its location, risk tolerance,
and facility operation. A larger facility may have a medical professional occupy-
ing the suite, while in smaller facilities, this task may be completed by persons
with some first aid training and consist of a less complex approach.
This section refers to pre-K through grade 12 facilities. For post-secondary
facilities, refer to ASHRAE Standard 170 or other standards, as appropriate. Due
to the increased possibility of an infected person entering a nurse’s suite, greater
caution and a higher level of air quality must be designed and installed similar to
an airborne isolation room in a hospital. While there are degrees of protection, air
should not be recirculated from this space to other occupied building areas.
Isolation of a nurse’s suite should consist of architectural barriers and con-
trolled pressure relationships between areas to mitigate the risk of airborne trans-
mission. The pressure of the space should be positive to outside but negative to
adjacent spaces, as this approach should reduce risk to the occupants. It is import-
ant to consider the pressure relationships, air changes, space exhaust, and opera-
tional policies and procedures.
Furthermore, the design approach should accommodate the safety and protec-
tion of the attending nurse or staff. When locating a nurse’s isolation suite, the safe
and efficient movement of a sick person from the nurse’s suite out of the building
needs to be considered to minimize the release of pathogens in the building.
Involved Parties
Design engineers, facility managers, architects, and building operations staff.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 17
Base Minimum
Wellness/nurse office or suite (any space intended for occupancy by indi-
viduals who are sick or suspected to be sick) should be maintained at a
negative pressure with respect to corridors and adjacent spaces.
Air may be recirculated within the space only but may not be returned
and recirculated to other spaces. All air leaving the space should be
exhausted to outdoors. Exhaust air may pass through energy recovery
devices serving other building areas being exhausted, as long as systems
comply with ASHRAE Standard 62.1. Exhaust air intakes should be fully
ducted to intakes in space.
Air recirculated within the space should be filtered through filter media
with minimum MERV rating of 13.
Maintain a minimum air change rate to space of six total air changes per
hour (ACH) and minimum of two ACH of outdoor air. All air in the wait-
ing areas and the isolation room should be exhausted when building or
space is occupied.
Special attention should be given to proper location of supply air diffusers
and return/exhaust air grilles.
Figure 3
Indicative wellness/nurse suite prototype configuration.
Source: Raj Setty/ASHRAE Epidemic Task Force. 2021. Schools and
universities. Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/
file%20library/technical%20resources/covid-19/ashrae-reopening-
schools-and-universities-c19-guidance.pdf.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
18 Design Guidance for Education Facilities
Improved IAQ
Create a school/building-specific nurse’s isolation suite. The number of
isolation rooms will depend on the school programming requirements.
Do not mix supply air and return air from isolation room with any other
spaces when in isolation mode.
Maintain a minimum clean ACH of 6 in all conditioned spaces in the
nurse’s suite, 10 ACH in the waiting room, and 12 ACH in the isolation
room(s). All air in the waiting areas and the isolation room should be
exhausted when building or space is occupied.
Exhaust directly to outdoors. Follow ASHRAE Standard 62.1 require-
ments to avoid re-entrainment of contaminated air. If there is a concern of
recirculation, HEPA filtration on exhaust could be added.
The nurse’s suite should be under negative air pressure in relation to
building corridors and adjacent spaces.
Follow applicable ASHRAE Standard 170’s most recent tables for gen-
eral outpatient spaces (Table 8-2) and 2019 California Mechanical Code
(Ventilation).
Supply air should have a minimum of MERV 13 or higher filtration.
Special attention should be given to proper location of supply air diffusers
and return/exhaust air grilles (low return is recommended). In the isola-
tion room, the exhaust grille should be located close to the patient in the
proper elevation.
Provisions for biohazard waste and personal sanitation including, but not
limited to, hand wash, showers, water closets, etc.
Provisions for PPE storage and application to mitigate the risk of PPE
becoming contaminated.
Advanced IAQ
Create school/building-specific nurse’s isolation suite(s) based on the
unique school population.
100% OA dedicated outdoor air unit (DOAU) with air-to-air energy
recovery (no cross contamination/carryover in the energy recovery heat
exchanger). The unit should be capable of switching to recirculation/min-
imum OA when applicable with the ability to provide and control the
desired thermal conditions (space temperature and humidity).
Treat as Airborne Infectious Isolation (AII) per ASHRAE Standard 170
and ASHRAE Handbook, Chapter 9 (2019).
ACH = 12 to 20.
Add UVGI to dedicated HVAC unit or other approved disinfection tech-
nology. Upper air room (with fan as an option) UVGI can be also consid-
ered, specifically in critical areas such as isolation and waiting rooms.
Dedicated bathrooms that should be kept under negative pressure in rela-
tion to adjacent spaces.
Nurse’s station infirmary beds should be defined based on the population
of the school (typically 1 bed /200 students).
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 19
Recommend locations of nurse’s office HVAC on an exterior wall.
Maintain pressure relationship for room, ante room, and corridor.
Directional airflow designer to consider the airflow pattern.
Establish an annual verification program to confirm airflows and pressure
relationships by a certified technician.
Follow maintenance and operations schedule established in ASHRAE
Standard 62.1.
Add a separate power supply for all equipment and ventilation to standby
power system.
Provide permanently mounted sensors for IAQ monitoring and occu-
pancy. At minimum, parameters such as CO
2
, total volatile organic com-
pounds (TVOCs), PM
2.5
, and PM
10
should be monitored.
Additional Guidance
ASHRAE. 2017. ASHRAE Standard 170-2017, Ventilation of healthcare facili-
ties. Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/technical-
resources/standards-and-guidelines/standards-addenda/ansi-ashrae-ashe-stan-
dard-170-2017-ventilation-of-health-care-facilities.
ASHRAE. 2022. ASHRAE Standard 62.1-2022, Ventilation and acceptable
indoor air quality. Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/
technical-resources/bookstore/standards-62-1-62-2.
ASHRAE Epidemic Task Force. 2021. Schools and universities. Peachtree Cor-
ners, GA: ASHRAE. https://www.ashrae.org/file%20library/technical%20re-
sources/covid-19/ashrae-reopening-schools-and-universities-c19-
guidance.pdf.
NIEHS. Handout 1: Infection control checklist for risk assessment and precau-
tions for construction & renovation. https://tools.niehs.nih.gov/wetp/public/
Course_download2.cfm?tranid=9806.
Classroom and Assembly Space
Air Distribution and Dilution Effectiveness
Overview
While it is possible to identify the location of the potential infector in some
applications, that is not applicable in a classroom. Any occupant may potentially
be an infector. Given that the potential infector could be anywhere in the room, the
best applied strategy should ensure there are no direct drafts that could concen-
trate infectious aerosols. Maintaining good mixing will also reduce thermal stress
and conform to energy standards such as ASHRAE/IES Standard 90.1 for dis-
charge air temperature requirements.
Involved Parties
Design engineers, facility managers, architects, and building operations staff.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
20 Design Guidance for Education Facilities
Base Minimum
Ensure air grilles and diffusers are in good operating condition and are
not configured such that they will create drafts.
For modifications or new distribution systems, follow ASHRAE/IES Stan-
dard 90.1, which limits discharge temperature to 20°F (11°C) above room
temperature.
Design intent should minimize cross-flow between occupants but maxi-
mize room volume dilution.
Minimum outside air should not be substituted with increased ventilation
effectiveness strategies.
Review temporary dividers impact on air distribution to avoid creation of
drafts and concentrations of flow.
Advanced IAQ
Follow ASHRAE Standard 55 requirements to maintain a maximum of
5.4°F (3°C) of temperature difference between the head and foot level of
the space and air velocity.
The ASHRAE Handbook—HVAC Applications recommends mixing;
however, care must be taken to minimize transfer air among occupants.
Consider vertical separation in flow patterns including, but not limited to,
supply air high and return air low, underfloor air distribution (UFAD),
and displacement ventilation (DV). Different strategies should be ana-
lyzed for different operating conditions in climate zones where both heat-
ing and cooling operation will be required during occupied periods.
Air cleaners may be considered to improve IAQ, but their impact on
existing distribution effectiveness should be reviewed.
CFD modeling can be used to consider different approaches and model
various classroom configurations and desk arrangements.
Additional Guidance
ASHRAE. 2019. ASHRAE/IES Standard 90.1-2019, Energy standard for build-
ings except low-rise residential buildings. Peachtree Corners, GA: ASHRAE.
https://www.ashrae.org/technical-resources/bookstore/standard-90-1.
ASHRAE. 2020. ASHRAE Standard 55-2020, Thermal environmental conditions
for human occupancy. Peachtree Corners, GA: ASHRAE. https://
www.ashrae.org/technical-resources/bookstore/standard-55-thermal-environ-
mental-conditions-for-human-occupancy.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 21
High Priority Tasks
IAQ Sensors with Data Aggregation Platform
Overview
IAQ sensors distributed throughout the building will provide a baseline IAQ
profile of the entire building. The goal of this section is to inform practitioners on
how to prepare sensors and interpret readings for an IAQ-centric HVAC system.
The driving force for our industry is energy efficiency, which has been the pre-
dominant underlying engineering design dogma. This must now be balanced with
a high level of indoor air quality for the health and welfare of the learners. The
best way to balance IAQ and energy efficiency is to deploy a suite of IAQ sensors
to provide a data-driven approach to proper HVAC operations.
The designer must, at a minimum, evaluate PM
2.5
/PM
1.0
/PM
0.5
, CO
2
, tem-
perature, TVOCs, and humidity, which all paint a picture of the optimal air quality
for the teaching space. Baseline should be created in spaces that reflect a mini-
mum of six months of data collection through both occupied and unoccupied
times. Sensors should be UL 2905 compliant.
Involved Parties
Design engineers, facility managers, architects, and building operations staff.
Base Minimum
IAQ sensors deployed at all HVAC main central air handling stations
during all periods of occupancy.
IAQ sensors deployed at 10% of the classrooms to provide an IAQ profile
of the distribution systems.
Readings should be taken daily, and trending data shared with a BMS or
web/cloud-based data repository and reporting platform. Design team to
set thresholds for CO
2
, TVOCs, and PM levels. Thresholds should incor-
porate time elements and be established on local outdoor air quality as the
baseline.
Monitor PM
2.5
, CO
2
, temperature, TVOCs, and humidity.
Establish an ongoing testing and verification program as per Table 8.1 in
ASHRAE Standard 62.1:
Inspection/Maintenance Task
ad. Verify the accuracy of permanently mounted sensors whose
primary function is outdoor air delivery monitoring, outdoor air
delivery verification, or dynamic minimum outdoor air control,
such as flow stations at an air handler and those used for demand
control ventilation, including CO
2
sensors. A sensor failing to
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
22 Design Guidance for Education Facilities
meet the accuracy specified in the O&M manual shall be recali-
brated or replaced. Performance verification shall include output
comparison to a measurement reference standard consistent with
those specified for similar devices in ASHRAE Standard 41.2 or
ASHRAE Standard 111.
Advanced IAQ
IAQ sensors deployed throughout the building at no less than one sensor
per 3000 ft
2
.
Readings should be taken every five minutes and trending data shared
with a BMS.
Data aggregation and analysis software to be provided to create an IAQ
daily profile.
BMS should calculate the PM
2.5
, CO
2
, temperature, TVOCs, humidity
levels of degradation from peak occupancy to baseline normal levels.
HVAC should be capable of adjustments to increase CADR levels to
bring the classroom IAQ to baseline levels within 60 minutes of peak.
Baseline algorithms should take IAQ alarms and adjust HVAC sequences
for flushing, higher ventilation, or airflow changes to improve the IAQ in
real time. Possibly incorporate totalizers for number of hours room is out-
side of specified parameters so that either scheduling or equipment can be
modified to improve IAQ.
Consider monitoring PM
10
, PM
1.0
, and different types of volatile organic
compounds.
Physically verify sensor accuracy annually.
Consider revising control strategy to maximize IAQ. If there is good outside
quality air of a suitable temperature and humidity, maximize outdoor air.
Additional Guidance
AIRNOW. 2022. Air quality index (AQI) basics. https://www.airnow.gov/aqi/aqi-
basics/.
ASHRAE. 2022. ASHRAE Standard 62.1-2022, Ventilation and acceptable
indoor air quality. Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/
technical-resources/bookstore/standards-62-1-62-2.
CDC. 2019. NIOSH pocket guide to chemical hazards. https://www.cdc.gov/
niosh/npg/npgd0103.html.
EPA. 2022. Creating healthy indoor air quality in schools. https://www.epa.gov/
iaq-schools.
IEQ Guidelines. 2022. Copy of all IAQ guidelines reports. https://ieqguide-
lines.org/table.html.
UC Davis Energy. 2020. Importance of ventilation in schools. YouTube video,
produced by University of California Davis Western Cooling Efficiency Cen-
ter. https://www.youtube.com/watch?v=F9hB9BgonHs.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 23
New HVAC Equipment to Achieve
ASHRAE-Recommended Air Change Rates
Overview
New HVAC systems should be designed to comply with the most current
adopted mechanical and building codes within the jurisdiction where the facility is
located, including the code-required minimum ventilation standard. In the absence
of a code official or authority having jurisdiction over the design and construction
of a new HVAC system, or an adopted code, ASHRAE recommends designing the
systems to provide the minimum ventilation rates in the breathing zone as deter-
mined using Table 6-1 in ASHRAE Standard 62.1, Ventilation and Acceptable
Indoor Air Quality.
Involved Parties
Design engineers, facility managers, and building operations staff.
Base Minimum
As determined in accordance with Table 6-1 in ASHRAE Standard 62.1-2019,
MERV 13 filters for all recirculated air.
Air Distribution
Design systems to provide well-mixed air. Avoid air velocities that create
drafts or create airflow across or from one occupant to another.
Space Total Air Changes Per Hour
Three to six ACH minimum during occupied periods. The maximum
should be based on design loads.
Reduced volume during unoccupied periods is acceptable to conform to
energy code requirements.
Air Cleaners
Consider air cleaners with HEPA filtration to supplement ventilation systems
and distribution design to ensure minimum space air change CADR levels are
met. This can include multiple air cleaners positioned to best provide air cleaning.
Noise
Design systems for maximum 40 dB in classrooms.
Equipment Motor Horsepower
Include a safety factor when sizing fan motors so the unit accommodates an
increase of 25% above design external static pressure in the future.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
24 Design Guidance for Education Facilities
Advanced IAQ
For Dedicated Outdoor Air Systems
Design the systems (equipment size and air distribution network) so they can
be set to a pandemic mode of operation and deliver 30% more ventilation air than
the code or base minimum. Filter ventilation air with MERV 13 filters.
For Central Station Air Handling Systems
Design the systems (equipment size and air distribution network) so they can be set
to a pandemic mode of operation and deliver 30% more ventilation air than the code or
base minimum. Filter all outdoor air and recirculated air with MERV 13 filters.
Design units with 100% outside air economizers so units can provide 100%
ventilation during times of the year when outside conditions can meet the HVAC
loads in the building and maintain thermal comfort.
Space total air changes per hour: six to eight ACH.
Air Cleaners
Consider air cleaners with HEPA filtration to supplement ventilation systems
and distribution design to ensure the minimum space air change CADR levels are
met. This should include an air cleaner positioned above the teacher’s desk or area
the teacher should occupy the most during a class.
Additional Guidance
ASHRAE. 2022. ASHRAE Standard 62.1-2022, Ventilation and acceptable
indoor air quality. Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/
technical-resources/bookstore/standards-62-1-62-2.
Hear-it.org. 2022. School noise detrimental to hearing and learning. https://
www.hear-it.org/school-noise-detrimental-hearing-and-learning.
Classroom-Level Air Cleaning
Overview
Air cleaners are intended to work with building ventilation systems and are
not to be used as a substitute for building ventilation. While they may assist in
removing infectious particles, they can present additional challenges and risks in
the space.
Benefits
The use of in-room air cleaners (either portable or permanently installed) may
help reduce concentrations of airborne particulate, including airborne pathogens,
from occupied spaces. In-room air cleaners utilizing HEPA filtration may effec-
tively remove nearly all airborne pathogens passing through the unit filter
Concerns
While in-room air cleaners are likely to help reduce airborne pathogen concentra-
tions, they also have implications for operations in the spaces served. Sound power
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 25
levels, potential negative impacts to space air distribution effectiveness, maintenance
personnel safety, and maintenance requirements all need to be considered.
Involved Parties
Design engineers, facility managers, architects, and building operations staff.
Base Minimum
Target code-required ventilation (ASHRAE Standard 62.1 requirements or
equivalent), good air distribution, and increased filtration efficiency.
Design Considerations
For buildings achieving the minimum actions above, addition of in-room air
cleaners may be considered on a case-by-case basis to achieve the owner’s defined
level of risk tolerance. Each type of classroom use case should be included in the
design of air cleaners that will accommodate the peak occupancy. For example,
music rooms and conference rooms should be evaluated for higher air cleaner
deployments.
Limited or No Existing Mechanical Ventilation
In cases where there is limited or no existing mechanical ventilation, provide
in-room air cleaners to provide maximum non-infectious air delivery equivalent
(NIADE) rate. Consideration must be given to air distribution in space, sound
power levels, and maintenance procedures.
Advanced IAQ
Introduce terminal or portable all-electric HEPA/UV machines in each class-
room.
Design Considerations
Target highest achievable NIADE rate for units that will not generate exces-
sive noise or negatively impact space air distribution (should not create drafts that
direct air across one occupant and toward others). Ensure flow patterns maximize
mixing of air in classrooms.
Maintenance Considerations
Relevant additions to maintenance schedule and operations training.
Develop maintenance policies for new/added equipment such as local air
cleaners, humidifiers, additional filtration in mechanical equipment, etc.
Portable Unit Specifications
UV-C light, minimum of 1200 microwatts/cm
2
HEPA filter
Cfm adjustable from 200 to 400 cfm
Noise sound level under NC 35
Power 110-volt plug in
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
26 Design Guidance for Education Facilities
Suggested Guidance for Portable Classroom Air Cleaner
Installation and Operations
Air cleaner location
Place the air cleaner in a centralized location and as close to the main
building HVAC return air grilles as possible.
For rooms with unit ventilators or HVAC units located near the win-
dows, place the air cleaner in the center of the room.
If there is noise or there are safety concerns with the electrical wires,
place the air cleaner near the teacher. Generally, adults can generate
more infectious particles than children under 14.
Make sure the airflow pattern is one way, from occupants to return
air. We want to minimize the recirculation of air amount occupants.
Location should be adjusted as the classroom furniture is reconfig-
ured. Place the air cleaner near the maximum number of students.
Air cleaner speeds during class
Make sure the air cleaner meets the classroom acoustics requirement
and does not hamper the students’ ability to hear the teacher.
Units have adjustable speeds. Utilize the lower speeds if there are
acoustical issues; otherwise, operate at maximum acoustically suit-
able speed.
Turn on units at maximum speed one hour before any occupied event
or start of class.
If there are any noticeable smells from cleaning products, run the
units until the smell dissipates. Cleaning products can increase the
level of TVOCs, which can be harmful at high concentrations.
Ensure unit placement will not cause additional interaction between
occupants and the equipment.
Air cleaner speeds after class
Air cleaner should be running at the full speed allowed during class
break and between classes for a minimum of 10 minutes.
Turn units off one hour after space is cleaned or is unoccupied.
Operate units at maximum speed after class.
Air cleaner operations for weekends
Keep units off during unoccupied times (i.e., weekends) unless
TVOC levels are high.
Turn air cleaners on one to two hours prior to class occupancy on
Mondays, if possible, at maximum speed.
Additional Guidance
Allen, J., J. Cedeno-Laurent, and S. Miller. 2020. Harvard-CU Boulder portable
air cleaner calculator for schools v1.3. https://docs.google.com/spreadsheets/
d/1NEhk1IEdbEi_b3wa6gI_zNs8uBJjlSS-86d4b7bW098/
edit#gid=1882881703.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 27
ASHRAE. 2021. ASHRAE position document on filtration and air cleaning.
Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/file%20library/
about/position%20documents/filtration-and-air-cleaning-pd-feb.2.2021.pdf.
ASHRAE. 2021. In-room air cleaner guidance for reducing Covid19 in air in your
space/room. Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/
file%20library/technical%20resources/covid-19/in-room-air-cleaner-guid-
ance-for-reducing-covid-19-in-air-in-your-space-or-room.pdf.
Restroom Exhaust and Air Filtration Upgrades
Overview
Restrooms present a challenge and risk in most schools. With the configura-
tion of most restrooms, it is not possible to maintain social distancing require-
ments and the spaces are higher traffic.
When a cohorting strategy is applied, restrooms are often overlooked, though
they are used by all groups, presenting a risk of transmission between otherwise
isolated groups.
Additionally, toilet flushing and other activities may generate aerosols that
may convey infectious particles. Due to the increased risk in these locations, there
may be additional consideration warranted to mitigation.
Involved Parties
Design engineers, facility managers, architects, and building operations staff.
Base Minimum
Ensure that all washroom fans are operating correctly and confirm that air
volumes are in accordance with ASHRAE Standard 62.1.
Ensure that washroom exhaust systems are operating continuously during
occupied periods and before and after the primary occupancy period.
Ensure that doors opening and closing will not negatively impact airflows
in the washroom. This is relevant where the washroom depends on trans-
fer air.
Advanced IAQ
Consider application of upper UVGI systems such as recirculating troffer
style systems and passive upper air UVGI.
Consider using air cleaners to achieve two additional air changes in bath-
rooms.
Consider using particulate sensors.
Consider expanding exhaust ductwork grilles to be placed above each
water closet. Where possible, installing grilles in the wall closer to the
fixture and breathing zone is preferred but may not be possible in many
locations.
Consider increasing exhaust rates to 15% above 62.
Consider lowering water closet partitions to floor.
Consider touchless plumbing fixtures.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
28 Design Guidance for Education Facilities
Additional Guidance
ASHRAE. 2022. ASHRAE Standard 62.1-2022, Ventilation and acceptable
indoor air quality. Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/
technical-resources/bookstore/standards-62-1-62-2.
Staff Training and Documentation
Organizational Platform
Overview
A dedicated school system-level program for IAQ should be established. A
maintenance and operational sequence must be adopted and strictly followed to
ensure pathogen mitigation efforts and general IAQ objectives are maintained.
Safety and health of all staff and students should be the fundamental basis for all
maintenance schedules. All maintenance procedures, schedules, adjustments,
repairs, upgrades, and replacements should be documented to provide transpar-
ency for all stakeholders.
Stakeholders
The maintenance should be assigned to a skilled, trained, and certified work-
force. The building automation system (BAS), if applicable, should include data
logging and summary reports to identify issues and make energy efficiency
improvements that do not degrade performance. However, all staff should be
aware of the agreed upon operational plans of the facility to ensure the designed
benefits are achieved.
Involved Parties
Design engineers, facility managers, architects, and building operations staff.
Base Minimum
Safety and Risk
All maintenance procedures should be evaluated for safety, given site-specific
equipment and associated safety concerns. Added safety procedures should be in
alliance with OSHA.
Develop a Primary Maintenance Schedule
ASHRAE Standard 62.1, Chapter 8, Operations and Maintenance, provides
the minimum maintenance activity and frequency for ventilation system equip-
ment and associated components.
Advanced IAQ
Develop a Comprehensive IAQ and Risk Mitigation Program
Similar to water quality testing, an air quality testing and monitoring system
should be established. Each jurisdiction should base their IAQ and risk mitigation
program on the goals of “good” air quality in their local region. The program pro-
file should account for outdoor contaminants as well as indoor pollutants. The
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 29
program should establish HVAC upgrades as part of the capital planning effort to
build systems to improve the air quality in the classroom environment. These sys-
tems should consider increased ventilation, better air filtration, better distribution
of clean air, air cleaners, and continuous monitoring.
Develop a Comprehensive Maintenance Schedule
ASHRAE Standard 180 establishes minimum HVAC inspection and mainte-
nance requirements that preserve a system’s ability to achieve acceptable thermal
comfort, energy efficiency, and indoor air quality in new and existing commercial
buildings. All maintenance personnel should consult ASHRAE Standard 180 to
develop a detailed site-specific plan.
Acceptable IAQ parameters should be developed in collaboration with your
HVAC professional and relevant authorities having jurisdiction.
Additional Guidance
ASHRAE. 2018. ASHRAE Standard 180-2018, Standard practice for inspection
and maintenance of commercial building HVAC systems. Peachtree Corners,
GA: ASHRAE. https://www.techstreet.com/ashrae/standards/ashrae-180-
2018?product_id=2016639.
ASHRAE. 2022. ASHRAE Standard 62.1-2022, Ventilation and acceptable
indoor air quality. Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/
technical-resources/bookstore/standards-62-1-62-2.
ASHRAE Epidemic Task Force. 2021. Schools & universities. Peachtree Corners,
GA: ASHRAE. https://www.ashrae.org/file%20library/technical%20re-
sources/covid-19/ashrae-reopening-schools-and-universities-c19-guid-
ance.pdf.
NEMI. 2022. Ventilation verification specification. https://www.nemionline.org/
ventilation-verification-specification/.
OSHA. 2022. Personal protective equipment. https://www.osha.gov/personal-pro-
tective-equipment.
UV-C/UVGI in Air Handling Equipment
Overview
UVC/UVGI equipment has been shown to be very effective in deactivating
viruses and other infectious agents. These systems produce light that may be
harmful to occupants, so they should be installed such that they will not affect the
occupants whether being installed inside an air handler, in the upper air zone of
the room, or in a recirculating configuration.
Properly sized and installed UVC/UVGI equipment may act as a supplemental
factor in the room’s clean air delivery, but it is important that it not replace proper
outside air ventilation as defined in ASHRAE Standard 62.1.
UVC/UVGI needs to be serviced regularly to ensure that the bulbs stay clean
and have not been affected by changes in temperature. The expected service life of
many of the bulbs will require regular changes, so access and cost should be con-
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
30 Design Guidance for Education Facilities
sidered along with the additional heat generated by the lamps themselves. As
more LED technology is developed, it is likely that the cost and maintenance costs
of the equipment will be reduced.
Involved Parties
Design engineers, facility managers, and building operations staff.
Base Minimum
Consider UV-C/UVGI in spaces that have high occupancy/frequent
changeover where it may not be practical to achieve recommended air
volumes.
UV-C/UVGI should be designed in coordination with a professional to
ensure the proper level of disinfection is occurring based on the airspeed
and UV-C intensity of airside equipment.
Provide a UVC fan motor interlock to energize UV-C only when the fan
is operational.
Provide a UV-C and access door safety interlock. UV-C should de-ener-
gize when door is opened for service.
Create a dedicated UV-C installation schedule with the following mini-
mum specified requirements:
AHU tag
Location
Peak airflow
Air velocity
Cross sectional area
Distance required
Distance available
System type
UV-C dose @ day 365(µW-sec/cm
2
)
UV-C intensity @ day 365(µW/cm
2
)
Service considerations should be reviewed on each installation to allow
for proper maintenance.
Advanced IAQ
Install UVC/UVGI in recirculated air systems.
Install high air UVGI in higher volume spaces.
Additional Guidance
ASHRAE. 2015. ASHRAE position document on filtration and air cleaning.
Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/file%20library/
about/position%20documents/filtration-and-air-cleaning-pd-feb.2.2021.pdf.
For further resources on UVC use, refer to the following:
International Ultraviolet Association (IUVA)
U.S. Environmental Protection Agency (EPA)
Research Triangle Institute (RTI)
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 31
ASHRAE. 2016. Chapter 17, Ultraviolet lamp systems. ASHRAE handbook—
HVAC systems and equipment. Peachtree Corners, GA: ASHRAE. https://
www.ashrae.org/file%20library/technical%20resources/covid-19/i-
p_s16_ch17.pdf.
ASHRAE. 2019. Chapter 62, Ultraviolet air and surface treatment. ASHRAE
handbook—HVAC applications. Peachtree Corners, GA: ASHRAE. https://
www.ashrae.org/file%20library/technical%20resources/covid-19/i-
p_a19_ch62_uvairandsurfacetreatment.pdf.
ASHRAE. 2020. ASHRAE position document on indoor air quality. Peachtree
Corners, GA:ASHRAE. https://www.ashrae.org/file%20library/about/posi-
tion%20documents/pd_indoor-air-quality-2020-07-01.pdf.
ASHRAE. 2022. ASHRAE positions infectious aerosols. Peachtree Corners, GA:
ASHRAE. https://www.ashrae.org/file%20library/about/position%20docu-
ments/pd_-infectious-aerosols-2022.pdf.
ASHRAE. 2020. ASHRAE Standard 185.1-2020, Method of testing UV-C lights
for use in air-handling units or air ducts to inactivate airborne microorgan-
isms. Peachtree Corners, GA: ASHRAE. https://www.techstreet.com/ashrae/
standards/ashrae-185-1-2020?product_id=2185612.
ASHRAE. 2020. ASHRAE Standard 185.2-2020, Method of testing ultraviolet
lamps for use in HVAC&R units or air ducts to inactivate microorganisms on
irradiated surfaces. Peachtree Corners, GA: ASHRAE. https://www.tech-
street.com/ashrae/standards/ashrae-185-2-2020?product_id=2185696.
Bahnfleth, W.P. 2020. Reducing infectious disease transmission with UVGI.
Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/file%20library/
professional%20development/learning%20portal/instructor-led%20training/
online%20instructor-led/final-4-21-2020-ashrae-one-hour-uvgi-course_se-
cured.pdf.
Illuminating Engineering Society. 2020. Guidance on the use of ultraviolet germi-
cidal irradiation (UVGI) in museum applications. IES WP-1-20. New York:
IES. https://store.ies.org/product/wp-1-20-ies-white-paper-guidance-on-the-
use-of-ultraviolet-germicidal-irradiation-uvgi-in-museum-applications/.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
32 Design Guidance for Education Facilities
Medium Priority Tasks
Humidification and Dehumidification Systems
Overview
Consider maintaining relative humidity (rh) at 40% to 60%. Optimal relative
humidity continues to be an area of active research. Dry air below 40% rh has
been shown to:
Reduce healthy immune system function (respiratory epithelium, skin,
etc.).
Increase transmission of some airborne viruses and droplets (COVID-19
still being studied).
Increase survival rate of pathogens.
Decrease effectiveness of hand hygiene and surface cleaning because of
surface recontamination or disinfectants drying too quickly.
Concerns
If restarting older humidifiers, take care to confirm proper moisture absorption
in the airstream.
Visually inspect humidification and dehumidification devices. Clean and
maintain to limit fouling and microbial growth. Measure relative humidity and
adjust system controls as necessary per ASHRAE Standard 62.1 Table 8-1 (g).
Watch interior spaces to confirm no condensation is occurring, which would
permit mold and moisture issues. Reducing economizer operation is not recom-
mended to improve minimum rh if it means losing negative pressure in rooms or
losing once-through airflow if those strategies are part of the surge plan.
Ensure adequate maintenance capacity and water treatment is available to
safely operate humidifying equipment.
Involved Parties
Design engineers, facility managers, and building operations staff.
Base Minimum
Design Considerations
Indoor relative humidity is a function of seasonal climate and building HVAC.
The range of 40% to 60% rh may reduce contagion and help those who are infected.
Summer classroom design guidelines: 75°F (24°C)/40% to 60% rh. Primary guid-
ance is to design to 50% rh in summer, depending on the classroom system.
During periods of time that the building is both occupied and unoccupied, it is
recommended that maximum humidity levels are addressed to not cause damage
to building materials that may be subject to damage at high humidity levels.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 33
Consider monitoring the humidity levels in a few classrooms within the build-
ing. Ensure that humidification systems do not generate an increase in particulate
matter.
Advanced IAQ
Design Considerations
Winter classroom design guidelines: 72°F (22°C)/40% to 50% rh. Primary
guidance in winter is 40% to 50% rh via humidifiers/active humidification (central
or local, depending on the classroom/space system). The humidity minimum,
humidifier, and sensor location should be made after consideration of envelope
design due to the potential for condensation within the building envelope.
The levels of 40% rh may be difficult to achieve in northern colder climates
without formation of condensate on glazing or within the building envelope.
Review of the building envelope design is crucial to ensure that damage to the
building envelope will not be created.
Summer classroom design guidelines: 75°F (24°C)/40% to 60% rh.
Energy Efficiency Offset Control Schemes for
Advanced IAQ
Overview
Generalizing for most HVAC systems, with the increase of more ventilation
air, except for economizer mode, it is sufficiently likely to expect higher energy
usage. As advanced air quality centers around maximizing the ventilation air and
disabling demand control ventilation systems, the logical result will be increased
energy to condition the increased outside air being brought into the building in
both the heating and cooling season.
With 8760 hours in a year, the best approach for energy efficiency during the
period of increased ventilation rates is to focus efforts on unoccupied times. In
some schools, this will be 6000+ hours per year. The energy efficiency programs
put in place should not diminish the indoor air quality by adverse ventilation
scheme changes.
Involved Parties
Design engineers, facility managers, building operations staff, and building
controls staff.
Base Minimum
Building management system with all HVAC and lighting integrated.
Focus on unoccupied hours and adjusting sequences to move to minimal
energy usage during unoccupied times.
Air cleaners for occupied mode operations in lieu of increasing ventila-
tion rates.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
34 Design Guidance for Education Facilities
Wider temperature bandwidth ranges for occupied zones 5% outside of
ASHRAE Standard 62.1.
Adjust the discharge temperatures from central air handling stations
based on the specific climate zone within 2% of ASHRAE Standard 62.1.
Advanced IAQ
Building management system with all HVAC, plumbing, equipment, and
lighting integrated.
Focus on unoccupied hours and adjusting sequences to move to minimal
energy usage during unoccupied times.
Air cleaners for occupied mode operations in lieu of increasing ventila-
tion rates.
Wider temperature bandwidth ranges for occupied zones 10% outside of
ASHRAE Standard 62.1.
Adjust the discharge temperatures from central air handling stations
based on the specific climate zone within 3% of ASHRAE Standard 62.1.
Enhanced air quality mode can be implemented into control systems.
This mode will revise CO
2
set points, run times, and system operation in
accordance with enhanced air quality parameters. This mode can be
quickly activated with one button during periods of elevated pathogen
risk. Alarms can be configured to occur on a regular basis to ensure that
the mode is not left on beyond the intended time frame.
Incorporate exhaust air heat recovery.
Additional Guidance
ASHRAE. ASHRAE advanced energy design guide—Achieving zero energy
series. Peachtree Corners, GA: ASHRAE. https://www.ashrae.org/technical-
resources/aedgs/zero-energy-aedg-free-download.
ASHRAE. 2021. ASHRAE Guideline 36-2021, High performance sequences of
operation for HVAC systems. Peachtree Corners, GA: ASHRAE. https://
www.techstreet.com/ashrae/standards/guideline-36-2021-high-performance-
sequences-of-operation-for-hvac-systems?product_id=2229690.
ASHRAE Epidemic Task Force. 2022. Building readiness. Peachtree Corners,
GA: ASHRAE. https://www.ashrae.org/file%20library/technical%20re-
sources/covid-19/ashrae-building-readiness.pdf.
Operable Windows
Overview
Any operable window usage for natural ventilation needs to be addressed and
agreed upon with your HVAC professional. Operable windows may be used to
supplement mechanical ventilation, or when no mechanical ventilation exists, nat-
ural ventilation should be considered with an understanding of limitations. While
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
Design Guidance for Education Facilities 35
operable windows by themselves will not provide consistent ventilation rates,
there are steps that may be added to improve the ventilation consistency.
Natural ventilation requires either an automated system that is maintained by
facilities or a highly trained staff to consistently open and close windows during
scheduled times.
Concerns
Security
•Noise
Consistency—Natural ventilation rates are dependent on several factors
including pressure and temperature differentials.
Seasonal Consistency—Occupants will be inclined to close the windows
during seasonal high and low temperature fluctuations.
Contamination
Air Distribution
Humidity
The best operational control of window opening criteria is to use a BMS with
dew point criteria if relevant to local climatic conditions. There should also be
provisions for the individual classrooms to have alarms or alerts to close the win-
dows based on dew point or other local criteria. In the absence of these automated
controls, please follow the instructions below if the school system is allowing the
teachers to open their windows based on their own personal preference.
Involved Parties
Design engineers, facility managers, architects, and building operations staff.
Base Minimum
Natural Ventilation
Natural ventilation should be performed in accordance with the corresponding
section within the adopted mechanical code or regional requirements—UMC Sec-
tion 402.2 or 402 IMC.
Negative Pressure
To provide a more consistent ventilation rate, the classroom can be operated at
a negative pressure, relative to the outside. With common windows open, either
manual or automatic, an outside air rate can be introduced. If the classroom is
independent of other structures, the ventilation rate can be consistent if the same
number of windows are opened during operation. If the classroom is attached to
other buildings, the exhaust will pull air from outside or from adjacent rooms
based on the path of least resistance. A negative pressure can be introduced by
adding exhaust fans or taking advantage of existing exhaust fans depending on
location.
Develop Manual Window Opening Guideline
Based on regional climate and safety considerations, the guide below may be
used as a starting point with school officials.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.
36 Design Guidance for Education Facilities
Classroom windows may be manually opened during class per the following
general guidelines during reopening operations.
Outside temperatures between 50ºF (10°C) and 90°F (32°C): Windows
can be opened.
HVAC units that are controlled by temperature will automatically
adjust. At lower temperatures, there will be excess running of units
during occupied hours.
Close windows during unoccupied hours and let HVAC systems run
per schedule.
Outside temperatures between 35°F (1.7°C) and 50°F (10°C): Windows
may be opened for 15 minutes each hour during occupied times.
Close windows when unoccupied.
If the classroom starts to feel too cold, adjust to 5–10 minutes open
per hour.
Outside temperatures below 35°F (1.7°C):
Windows can be opened at 50% for 15 minutes every 2 hours.
If classrooms have no fresh air, open windows at 50% every 15 min-
utes every hour. Monitor any water piping and sprinkler piping for
freeze potential.
If the classroom starts to feel too cold, adjust to 5–10 minutes open
per hour.
Classroom windows MUST be closed during unoccupied hours and
weekends.
Close windows if it is raining or is a humid day to prevent any mold
growth.
Advanced IAQ
Automated natural ventilation systems may be considered to provide con-
sistent open times. Advanced systems may be linked to a variety of
indoor and outdoor climate sensors.
Occupant indicators may be provided to indicate to occupants that the
windows should be open.
Security indicators may be useful to ensure that windows are closed. This
may be accomplished with the addition of end switches on the windows
to verify that they are closed.
© 2023 ASHRAE (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE's prior written permission.